AFDD TECHNICAL DATA

Download Catalogue pages, return to Home page or Contact us now.

AFDD 2 Pole Type A & Type AKV
                         Dimensions                                  Contact Assignments          
  Number of Poles
  Rated voltage (AC)                    
  Rated Current (AC)
  Rated frequency
  Rated residual current (IΔn)
  Working voltage range of test circuit
  Surge current (8/20μs) Type A
  Surge current (8/20μs) Type AKV
  Short circuit resistance:
          Ratings 10 to 25A
          Ratings 32 to 40A
          Maximum fuse size
  Arc fault diconnection times based on
  load current (EN62606)
          2.5A
            5A
          10A
          16A
          32A
          40A
  Neutral position 
  Terminal capacity
  Ambient temperature 
  Pollution degree (EN60664)
  Protection class (installed)
  Rail mounting (DIN)
  Design standards 
  2 protected poles
  230V 50Hz
  10A to 40A
  50Hz
  30mA Type A
  196-253V
  0.25kA
  3kA

  10kA
  6kA
  100A gG


  <1s
  <0.5s
  <0.25s
  <0.15s
  <0.12s
  <0.12s
  Right or Left	
  1mm2 to 25mm2
  -250C to 400C
  2
  IP40
  35mm
  EN2606/EN61009
          Click for large image

NOTE: Supply must be connected to terminals 2 & 4
          Load must be connected to terminals 1 & 3