Distribution Equipment Switchgear
Enclosed Switch-fuses:
- 3 switched poles * + BS 88 fuse links + Neutral link (unswitched)
- 4 switched poles * + BS 88 fuse links + copper link (switched)
Enclosed Switches:
- 3 switched poles* + Neutral link (unswitched)
- 4 switched poles* + Neutral link (unswitched)
Switchgear accessories Technical data Download this page - pdf
*Note:
Regulation 537.1.1 Note 1
Table 537.4(3) Suitable for on-load switching and isolation in TN-C-S and TN-S systems meeting the requirements o Regulation 461.2
- Ratings up to 630A
- Padlockable handle
- Indoor Installation
- IP65 Steel Enclosure
- Door Interlocked
- Gland Plate Entry
- UK Assembly
Switch supplied with incoming terminal shrouds.
If you require additional terminal shrouds, please order separately.
Refer to the Accessories tab.
Product Standard: EN60947-3
3 Pole Enclosed Switch-Fuses Ratings @ 35° C for Cable < 70° C and CSA* |
Refer to Technical Data for additional information |
AC22A Poles Amps Cable csa mm² Reference |
3 20 2.5 ASF-3020 3 32 6 ASF-3032 3 63 16 ASF-3063 3 100 50 ASF-3100 3 160 70 ASF-3160 3 200 95 ASF-3200 3 250 120 ASF-3250 3 400 240 ASF-3400 3 630 2 x 185 ASF-3630 |
3 Pole Enclosed Switches Ratings @ 35° C for Cable < 70° C and CSA* |
Refer to Technical Data for additional information |
AC22A Poles Amps Cable csa mm² Reference |
3 20 4 AS-3020 3 32 6 AS-3032 3 63 16 AS-3063 3 100 35 AS-3100 3 160 70 AS-3160 3 200 95 AS-3200 3 250 120 AS-3250 3 400 240 AS-3400 3 630 2 x 185 AS-3630 |
* Note:
The cable csa above is based on the requirements of 60947-3 - maximum conductor temperature 70° C.
Refer to regulation 523 Current carrying capacity requirements for cables.
4 Pole Enclosed Switch-Fuses Ratings @ 35° C for Cable < 70° C and CSA* |
Refer to Technical Data for additional information |
AC22A Neutral Pole Poles Amps Cable csa mm² Reference Position |
4 63 16 ASF-4063 On the Left 4 100 50 ASF-4100 On the Left 4 160 70 ASF-4160 On the Left 4 200 95 ASF-4200 On the Right 4 250 120 ASF-4250 On the Right 4 400 240 ASF-4400 On the Right 4 630 2 x 185 ASF-4630 On the Right |
The position of the neutral pole cannot be changed The neutral pole copper link must not be replaced with a fuse link |
4 Pole Enclosed Switches Ratings @ 35° C for Cable < 70° C and CSA* |
Refer to Technical Data for additional information |
AC22A Neutral Pole Poles Amps Cable csa mm² Reference Position |
4 100 50 AS-4100 On the Left 4 160 70 AS-4160 On the Left 4 200 95 AS-4200 On the Left 4 250 120 AS-4250 On the Left 4 400 240 AS-4400 On the Left 4 630 2 x 185 AS-4630 On the Left |
The position of the neutral pole cannot be changed |
* Note:
The cable csa above is based on the requirements of 60947-3 - maximum conductor temperature 70° C.
Refer to regulation 523 Current carrying capacity requirements for cables.