Distribution Equipment Switchgear

Enclosed Switch-fuses:

  • 3 switched poles * + BS 88 fuse links + Neutral link (unswitched)
  • 4 switched poles * + BS 88 fuse links + copper link (switched)

Enclosed Switches:

  • 3 switched poles* + Neutral link (unswitched)
  • 4 switched poles* + Neutral link (unswitched)

Switchgear accessories Technical data Download this page - pdf

*Note:
Regulation 537.1.1 Note 1
Table 537.4(3) Suitable for on-load switching and isolation in TN-C-S and TN-S systems meeting the requirements o Regulation 461.2

  • Ratings up to 630A
  • Padlockable handle
  • Indoor Installation
  • IP65 Steel Enclosure
  • Door Interlocked
  • Gland Plate Entry
  • UK Assembly

Switch supplied with incoming terminal shrouds.
If you require additional terminal shrouds, please order separately.
Refer to the Accessories tab.

Product Standard: EN60947-3

3 Pole Enclosed Switch-Fuses
Ratings @ 35° C for Cable < 70° C and CSA*
Refer to Technical Data for additional information
	            AC22A
   Poles         Amps          Cable csa mm²                           Reference
      3           20                 2.5                             ASF-3020
      3           32                  6                               ASF-3032
      3           63                 16                              ASF-3063
      3          100                50                              ASF-3100
      3          160                70                              ASF-3160
      3          200                95                              ASF-3200
      3          250               120                             ASF-3250
      3          400               240                             ASF-3400
      3          630            2 x 185                          ASF-3630
3 Pole Enclosed Switches
Ratings @ 35° C for Cable < 70° C and CSA*
Refer to Technical Data for additional information
	            AC22A
   Poles         Amps          Cable csa mm²                           Reference
      3           20                  4                               AS-3020
      3           32                  6                               AS-3032
      3           63                 16                              AS-3063
      3          100                35                              AS-3100
      3          160                70                              AS-3160
      3          200                95                              AS-3200
      3          250               120                             AS-3250
      3          400               240                             AS-3400
      3          630            2 x 185                          AS-3630

* Note:
The cable csa above is based on the requirements of 60947-3 - maximum conductor temperature 70° C.
Refer to regulation 523 Current carrying capacity requirements for cables.

4 Pole Enclosed Switch-Fuses
Ratings @ 35° C for Cable < 70° C and CSA*
Refer to Technical Data for additional information
	            AC22A                                                                           Neutral Pole
   Poles         Amps          Cable csa mm²              Reference               Position
     4           63                 16                    ASF-4063        On the Left
     4          100                50                    ASF-4100        On the Left
     4          160                70                    ASF-4160        On the Left
     4          200                95                    ASF-4200        On the Right
     4          250               120                   ASF-4250        On the Right
     4          400               240                   ASF-4400        On the Right
     4          630            2 x 185                ASF-4630        On the Right
The position of the neutral pole cannot be changed
The neutral pole copper link must not be replaced with a fuse link
4 Pole Enclosed Switches
Ratings @ 35° C for Cable < 70° C and CSA*
Refer to Technical Data for additional information
	            AC22A                                                                           Neutral Pole
   Poles         Amps          Cable csa mm²              Reference               Position
     4          100                50             AS-4100       On the Left
     4          160                70             AS-4160       On the Left
     4          200                95             AS-4200       On the Left
     4          250               120            AS-4250       On the Left
     4          400               240            AS-4400       On the Left
     4          630            2 x 185         AS-4630       On the Left
The position of the neutral pole cannot be changed

* Note:
The cable csa above is based on the requirements of 60947-3 - maximum conductor temperature 70° C.
Refer to regulation 523 Current carrying capacity requirements for cables.