RCBOs Type A
Type A residual current
Regulation 531.3.3 Tripping on:
- 50Hz sinusoidal AC
- Pulsating DC
- Pulsating DC superimposed on smooth DC < 6 mA.
Note: Type A RCDs do not detect smooth DC.
General Non-delay characteristics for final circuits. Ordering reference: see the tables on this page.
RCD selection and application RCBO accessories Technical data Download this page - pdf
General Non-delay characteristics for final circuits.
Ordering reference: see below
Product Standard: EN61009-1
Approvals: 2 Pole VDE
1 pole 230V RCBO "B" Curve Type A 10 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
1 1 6 30mA RCBO1-B06/003/1-A 1 1 10 30mA RCBO1-B10/003/1-A 1 1 16 30mA RCBO1-B16/003/1-A 1 1 20 30mA RCBO1-B20/003/1-A 1 1 25 30mA RCBO1-B25/003/1-A 1 1 32 30mA RCBO1-B32/003/1-A 1 1 40 30mA RCBO1-B40/003/1-A 1 1 45 30mA RCBO1-B45/003/1-A |
1 pole + N 230V RCBO "B" Curve Type A 10 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
2 2 6 30mA DRCBO-3B06/0.03/1N-A 2 2 10 30mA DRCBO-3B10/0.03/1N-A 2 2 16 30mA DRCBO-3B16/0.03/1N-A 2 2 20 30mA DRCBO-3B20/0.03/1N-A 2 2 25 30mA DRCBO-3B25/0.03/1N-A 2 2 32 30mA DRCBO-3B32/0.03/1N-A 2 2 40 30mA DRCBO-3B40/0.03/1N-A |
1 pole 230V RCBO "C" Curve Type A 10 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
1 1 6 30mA RCBO1-C06/003/1-A 1 1 10 30mA RCBO1-C10/003/1-A 1 1 16 30mA RCBO1-C16/003/1-A 1 1 20 30mA RCBO1-C20/003/1-A 1 1 25 30mA RCBO1-C25/003/1-A 1 1 32 30mA RCBO1-C32/003/1-A 1 1 40 30mA RCBO1-C40/003/1-A 1 1 45 30mA RCBO1-C45/003/1-A |
1 pole + N 230V RCBO "C" Curve Type A 10 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
2 2 6 30mA DRCBO-3C06/0.03/1N-A 2 2 10 30mA DRCBO-3C10/0.03/1N-A 2 2 16 30mA DRCBO-3C16/0.03/1N-A 2 2 20 30mA DRCBO-3C20/0.03/1N-A 2 2 25 30mA DRCBO-3C25/0.03/1N-A 2 2 32 30mA DRCBO-3C32/0.03/1N-A 2 2 40 30mA DRCBO-3C40/0.03/1N-A |
Application Notes:
a) 1 pole + N RCBOs are not suitable for single phase IT systems.
b) Center tapped (CT) transformer supplies for fixed equipment:
Use 2 pole RCCB + 2 pole MCBs. For 110V supplies, use 110v RCCBs.
3 pole + N 400V RCBO "B" Curve Type A 6 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
4 4 6 30mA DRCBO-4B06/0.03/3N-A 4 4 10 30mA DRCBO-4B10/0.03/3N-A 4 4 16 30mA DRCBO-4B16/0.03/3N-A 4 4 20 30mA DRCBO-4B20/0.03/3N-A 4 4 25 30mA DRCBO-4B25/0.03/3N-A 4 4 32 30mA DRCBO-4B32/0.03/3N-A 5 4 40 30mA DRCBO-4B40/0.03/3N-A |
3 pole + N 400V RCBO "C" Curve Type A 6 kA |
Time/Current characteristic: General Non-delay |
Modules Poles Amps Sensitivity Reference |
4 4 6 30mA DRCBO-4C06/0.03/3N-A 4 4 10 30mA DRCBO-4C10/0.03/3N-A 4 4 16 30mA DRCBO-4C16/0.03/3N-A 4 4 20 30mA DRCBO-4C20/0.03/3N-A 4 4 25 30mA DRCBO-4C25/0.03/3N-A 4 4 32 30mA DRCBO-4C32/0.03/3N-A 5 4 40 30mA DRCBO-4C40/0.03/3N-A |
Application Notes:
3 pole + N RCBOs must be used with a Neutral conductor (4 wire system).